By the MassBid Estimation team · Reviewed by a senior estimator with 10+ years of experience · Published · Updated
In short
Pipe is named by nominal size, which is not its real diameter. For steel and PVC pipe up to 12 in., the outside diameter is fixed for each nominal size and the schedule sets the wall: 1 in. pipe is 1.315 in. outside, with a 0.133 in. wall in Schedule 40 and 0.179 in. in Schedule 80. From 14 in. up, the outside diameter equals the nominal size. Copper tube is different: its outside diameter is always 1/8 in. more than the nominal size (1 in. copper is 1.125 in. outside), and Type K, L and M set the wall, K thickest and M thinnest.
- 1 in. Schedule 40
- 1.315 in. OD, 0.133 in. wall, 1.049 in. ID, 1.68 lb/ft
- 2 in. Schedule 40
- 2.375 in. OD, 0.154 in. wall, 2.067 in. ID, 3.65 lb/ft
- 4 in. Schedule 40
- 4.500 in. OD, 0.237 in. wall, 4.026 in. ID, 10.79 lb/ft
- PVC
- Same OD and wall as steel of the same schedule (ASTM D1785)
- Copper
- OD = nominal + 1/8 in.; 3/4 in. Type L = 0.875 in. OD, 0.045 in. wall
- Copper colors
- Type K green, Type L blue, Type M red
- Schedule vs STD
- STD = Sch 40 through 10 in.; XS = Sch 80 through 8 in.
Nominal pipe size is not the real size
Every pipe estimator learns this early: the size on the drawing is a name, not a measurement. Steel and PVC follow nominal pipe size (NPS). For each size up to 12 in. the outside diameter is fixed, so fittings fit, and the schedule changes only the wall, and with it the inside diameter. From 14 in. up, the outside diameter is the nominal size. Copper tube follows its own rule: the outside diameter is the nominal size plus 1/8 in.
| Nominal size | Steel or PVC pipe OD | Copper tube OD |
|---|---|---|
| 1/2 in. | 0.840 in. | 0.625 in. |
| 3/4 in. | 1.050 in. | 0.875 in. |
| 1 in. | 1.315 in. | 1.125 in. |
| 2 in. | 2.375 in. | 2.125 in. |
| 4 in. | 4.500 in. | 4.125 in. |
| 6 in. | 6.625 in. | 6.125 in. |
Schedule 40 and Schedule 80 pipe chart (steel and PVC)
| Size | OD | Sch 40 wall | Sch 40 ID | Sch 40 steel lb/ft | Sch 80 wall | Sch 80 ID | Sch 80 steel lb/ft |
|---|---|---|---|---|---|---|---|
| 1/8" | 0.405 | 0.068 | 0.269 | 0.24 | 0.095 | 0.215 | 0.31 |
| 1/4" | 0.540 | 0.088 | 0.364 | 0.42 | 0.119 | 0.302 | 0.54 |
| 3/8" | 0.675 | 0.091 | 0.493 | 0.57 | 0.126 | 0.423 | 0.74 |
| 1/2" | 0.840 | 0.109 | 0.622 | 0.85 | 0.147 | 0.546 | 1.09 |
| 3/4" | 1.050 | 0.113 | 0.824 | 1.13 | 0.154 | 0.742 | 1.47 |
| 1" | 1.315 | 0.133 | 1.049 | 1.68 | 0.179 | 0.957 | 2.17 |
| 1-1/4" | 1.660 | 0.140 | 1.380 | 2.27 | 0.191 | 1.278 | 3.00 |
| 1-1/2" | 1.900 | 0.145 | 1.610 | 2.72 | 0.200 | 1.500 | 3.63 |
| 2" | 2.375 | 0.154 | 2.067 | 3.65 | 0.218 | 1.939 | 5.02 |
| 2-1/2" | 2.875 | 0.203 | 2.469 | 5.79 | 0.276 | 2.323 | 7.66 |
| 3" | 3.500 | 0.216 | 3.068 | 7.58 | 0.300 | 2.900 | 10.25 |
| 3-1/2" | 4.000 | 0.226 | 3.548 | 9.11 | 0.318 | 3.364 | 12.50 |
| 4" | 4.500 | 0.237 | 4.026 | 10.79 | 0.337 | 3.826 | 14.98 |
| 5" | 5.563 | 0.258 | 5.047 | 14.62 | 0.375 | 4.813 | 20.78 |
| 6" | 6.625 | 0.280 | 6.065 | 18.97 | 0.432 | 5.761 | 28.57 |
| 8" | 8.625 | 0.322 | 7.981 | 28.55 | 0.500 | 7.625 | 43.39 |
| 10" | 10.750 | 0.365 | 10.020 | 40.48 | 0.594 | 9.562 | 64.43 |
| 12" | 12.750 | 0.406 | 11.938 | 53.52 | 0.688 | 11.374 | 88.63 |
| 14" | 14.000 | 0.438 | 13.124 | 63.44 | 0.750 | 12.500 | 106.13 |
| 16" | 16.000 | 0.500 | 15.000 | 82.77 | 0.844 | 14.312 | 136.61 |
| 18" | 18.000 | 0.562 | 16.876 | 104.67 | 0.938 | 16.124 | 170.92 |
| 20" | 20.000 | 0.594 | 18.812 | 123.11 | 1.031 | 17.938 | 208.87 |
| 24" | 24.000 | 0.688 | 22.624 | 171.29 | 1.219 | 21.562 | 296.58 |
Standard weight (STD) and extra strong (XS) are older names still used on drawings and in the AISC tables. STD has the same wall as Schedule 40 up to 10 in., and XS the same as Schedule 80 up to 8 in.; above those sizes, check which one the specification means. Structural pipe columns and bollards in the steel shapes chart use the same sizes.
Copper tube chart: Type K, L and M
| Size | OD | K wall | K ID | K lb/ft | L wall | L ID | L lb/ft | M wall | M ID | M lb/ft |
|---|---|---|---|---|---|---|---|---|---|---|
| 1/4" | 0.375 | 0.035 | 0.305 | 0.133 | 0.030 | 0.315 | 0.126 | – | – | – |
| 3/8" | 0.500 | 0.049 | 0.402 | 0.269 | 0.035 | 0.430 | 0.198 | 0.025 | 0.450 | 0.144 |
| 1/2" | 0.625 | 0.049 | 0.527 | 0.344 | 0.040 | 0.545 | 0.285 | 0.028 | 0.569 | 0.203 |
| 5/8" | 0.750 | 0.049 | 0.652 | 0.418 | 0.042 | 0.666 | 0.362 | – | – | – |
| 3/4" | 0.875 | 0.065 | 0.745 | 0.641 | 0.045 | 0.785 | 0.455 | 0.032 | 0.811 | 0.328 |
| 1" | 1.125 | 0.065 | 0.995 | 0.837 | 0.050 | 1.025 | 0.655 | 0.035 | 1.055 | 0.464 |
| 1-1/4" | 1.375 | 0.065 | 1.245 | 1.04 | 0.055 | 1.265 | 0.884 | 0.042 | 1.291 | 0.681 |
| 1-1/2" | 1.625 | 0.072 | 1.481 | 1.36 | 0.060 | 1.505 | 1.14 | 0.049 | 1.527 | 0.94 |
| 2" | 2.125 | 0.083 | 1.959 | 2.06 | 0.070 | 1.985 | 1.75 | 0.058 | 2.009 | 1.46 |
| 2-1/2" | 2.625 | 0.095 | 2.435 | 2.92 | 0.080 | 2.465 | 2.48 | 0.065 | 2.495 | 2.03 |
| 3" | 3.125 | 0.109 | 2.907 | 4 | 0.090 | 2.945 | 3.33 | 0.072 | 2.981 | 2.68 |
| 3-1/2" | 3.625 | 0.120 | 3.385 | 5.12 | 0.100 | 3.425 | 4.29 | 0.083 | 3.459 | 3.58 |
| 4" | 4.125 | 0.134 | 3.857 | 6.51 | 0.114 | 3.897 | 5.38 | 0.095 | 3.935 | 4.66 |
| 5" | 5.125 | 0.160 | 4.805 | 9.67 | 0.125 | 4.875 | 7.61 | 0.109 | 4.907 | 6.66 |
| 6" | 6.125 | 0.192 | 5.741 | 13.87 | 0.140 | 5.845 | 10.2 | 0.122 | 5.881 | 8.91 |
| Type | Color code | Wall | Typical use |
|---|---|---|---|
| K | Green | Thickest | Underground water service, high-pressure lines |
| L | Blue | Medium | Interior domestic water, hydronic heating and cooling, the default on most commercial jobs |
| M | Red | Thinnest | Interior low-pressure water where the code and specification allow it |
| DWV | Yellow | Thin | Drain, waste and vent only |
Hanger spacing for a pipe takeoff
Hangers are counted, not guessed. The maximum horizontal spacing in the International Plumbing Code, Table 308.5, is:
| Pipe | Maximum horizontal spacing |
|---|---|
| Steel pipe | 12 ft |
| Copper tube, 1-1/4 in. and smaller | 6 ft |
| Copper tube, 1-1/2 in. and larger | 10 ft |
| PVC pipe | 4 ft |
Pipe run calculator
Pick a material and size and enter the run length. The calculator gives the outside and inside diameter, the weight of the pipe, the weight of the water it holds (for hanger loads) and the number of hangers at code spacing.
Pipe run calculator
- Outside / inside diameter
- 1.125 / 1.025 in.
- Pipe weight, empty
- 66 lb (0.655 lb/ft)
- Water in the run
- 4.3 gal (36 lb)
- Hangers, horizontal run
- 18 at 6 ft max
Inside diameter = OD − 2 × wall. Hangers = run ÷ spacing, rounded up, + 1, at the maximum horizontal spacing in IPC Table 308.5 (steel 12 ft; copper 6 ft up to 1-1/4 in. and 10 ft from 1-1/2 in.; PVC 4 ft). Your code edition, the engineer's specification and MSS SP-58 can call for closer spacing, and every change of direction and valve needs support of its own.
How estimators take off piping
- Measure pipe by system, material and size in linear feet: domestic cold and hot water, waste, vent, storm, gas, heating water and chilled water separately, because each has its own material, joint and insulation.
- Count every fitting and valve by size: elbows, tees, reducers, couplings, unions and valves. On small-bore copper, fittings and joints can take more labor than the pipe itself.
- Add the risers. Plans show horizontal runs; vertical pipe comes from the floor-to-floor heights and the riser diagram.
- Count hangers, sleeves and firestopping from the run lengths and every wall and floor the pipe passes through.
- Measure insulation by pipe size and thickness from the specification table, not as one line.
Getting a piping takeoff done
We take off and price piping for plumbing, HVAC and site utilities, by system, material and size, with fittings, valves, hangers and insulation, and marked-up drawings. See MEP estimating or send the drawings for a free quote.
Common questions
1.315 in. The wall is 0.133 in., so the inside diameter is 1.049 in. Steel weighs 1.68 lb per foot.
2.375 in. for steel or PVC pipe of any schedule. The wall is 0.154 in. in Schedule 40 and 0.218 in. in Schedule 80. 2 in. copper tube is 2.125 in. outside.
4.500 in. outside diameter, 0.237 in. wall and 4.026 in. inside diameter. Steel weighs 10.79 lb per foot.
For the same nominal size the outside diameter is the same; Schedule 80 has a thicker wall, so a smaller inside diameter, higher pressure rating and more weight. 2 in. Schedule 40 has a 0.154 in. wall; Schedule 80 has 0.218 in.
Yes for Schedule 40 and 80 PVC under ASTM D1785: it has the same outside diameter and minimum wall as steel pipe of the same nominal size and schedule, so the same chart applies. It weighs much less.
0.875 in. Copper tube OD is always the nominal size plus 1/8 in. Type L 3/4 in. has a 0.045 in. wall and weighs 0.455 lb per foot.
Wall thickness. Type K (green) is thickest and is used underground; Type L (blue) is the usual choice for interior water and hydronic piping; Type M (red) is thinnest, for low-pressure interior water where the code allows. All three have the same outside diameter for a given size.
Under IPC Table 308.5, horizontal steel pipe at no more than 12 ft, copper tube 1-1/4 in. and smaller at 6 ft, copper 1-1/2 in. and larger at 10 ft, and PVC at 4 ft. Specifications and other codes can require closer spacing.
Nominal pipe size is a historical name kept so fittings stay interchangeable. For steel and PVC up to 12 in., the outside diameter was fixed and only the wall changes by schedule; from 14 in. up, the OD equals the nominal size. Copper tube OD is the nominal plus 1/8 in.